40kva three phase high voltage power supply ups (3C3 Series)

40kva three phase high voltage power supply ups (3C3 Series)
Product Detailed
1.40kva three phase high voltage power supply ups 2.40kva/32kw,380/400/415vac 3.high efficiency 4.wide input range 5.CE&ROHS

40kva three phase high voltage power supply ups (3C3 Series)             

The excellent performance:

1.IGBT based , high frequency rectifier and inverter design to achieve up to 93%-94% efficiency (Mains mode and battery mode),and low input current THD(>3%)

2. ECO mode to achieve up to 98% efficiency for energy saving.

3. Strong over load capability,10 minutes for 125% overload, and 1 minute for 150% overload.

4. wide input range which is suitable for very unstable power supply situation.

5. Generator input acceptable.

6. Power Factor Correction Achieve input PF 0.99.

High performance DSP processor

 The digital Ti DSP controlling chip provides precise data processing capability with excellent performance in output and reliability.

Flexible battery arrangement

    Flexible arrangement of the amount of accumulators in each battery (32,30,or 28)can be achieved through the parameter resetting in the Centrio 3C3 series UPS, which effectively solves the question that the damage of some individual cell may influence the life of the whole battery until by eliminating the damaged ones from the unit in the process of using UPS.

N+X parallel redundancy (compatible to battery share in the parallel mode)

      The maximum of the inbuilt parallel mode is 6 to 8 UPS without any other external accessories, which helps the customer to extend the system capacity with low cost. N stands for the minimum amount of UPS in the load and X stands for the amount of the redundant UPS in the system. The bigger the number of X is, the higher the reliability of the system.

The advanced controlling strategy is adopted to save the custom’s investment by sharing a battery until in the parallel redundancy mode.

Excellent performance in industrial environment protection

   Just with the standard product, IP21 protection level (protecting the machine from the intrusion of solid material with the diameter large than 12mm or the water drops) is achieved. If a higher protection level is required, the optional dust-proof accessories can help to increase the protection level in industrial environment and safeguard the UPS’s security of operation in bad environment.

 Technical specification

Product Series

 

Centrio 3C3 20-80KVA

Model

 

3C3 20K

3C3C 30K

3C3 40K

3C3 60K

3C3 80K

Capacity

VA/W

20KVA/16KW

30KVA/24KW

40KVA/32KW

60KVA/48KW

80KVA/64KW

Input

Connection

3-Phase + N + G

Rectifier Type

IGBT-based Controlled PFC

Input Voltage

380(-45%~ +25%)VAC(when input voltage<75%, output power derating is required)

Input Frequency

50 or 60 Hz (Accepted from 40 to 70Hz)

Input Current THD

3%

Input Power Factor

≥0.99

Bypass Voltage

380(-15%~ +15%)VAC

380(-20%~ +15%)VAC

Output

Inverter Type

IGBT-based

Output Voltage

380/400/415VAC

Output Frequency

50Hz/60Hz±8%track bypass frequency input ;when input frequency exceeds ±8% or under the mode of battery power supply, frequency output should be±0.1%of nominal

Output Voltage THD

1% (max)

Max.Load Crest Factor

3:1

Transient Volt.Resp

10ms to recover ± 5% of Nominal Voltage for 0% to 100% or 100% to 0% step load

Max.Leading PF Load

Up to 0.9

Overload Capability

≥10min  110%<Load125%

≥1min   125%<Load150%

Nominal battery voltage/Rated charging voltage

Battery Type

VRLA (Valve Regulated Lead Acid)

28 Pcs

±168VDC/±189VDC

30 Pcs

±180VDC/±202.5VDC

32 Pcs

±192VDC/±216VDC

Efficiency

AC Mode

Up to 93%

Up to 94%

Battery Mode

Up to 93%

Up to 94%

ECO Mode

Up to 98%

Operating Environment

Storage Temp

-25 to 55°C

Operating Temp

0 to 40°C

Ambient Humidity

0 to 95% (non_condensing)

Altitude

≤1000m

Main unit

Dimension(W×D×H) mm

420×643×956

470×710×1150

470×710×1150

600×800×1850

600×800×1850

Weight(Kg)

82

110

114

282

306

Customer Feedback

Our R&D team have tested your UPS, they are satisfied with the performance of the sample. All the test

results are complying with the specification. We are highly appreciated it. --- N. Raja (from Chennai, India)

We are quite impressive with the IGBT function of this UPS. We are now trying to apply this model on our

telecommunication systems. --- Robert Alles (from Munich, Germany)

 

Order information

Trade term: FOB Shenzhen / Hongkong

Delivery time: 7-21 days after confirmed the order

Packaging Detail:Standard export carton or OEM package

 

Warranty

1 years since the date of purchase  

Warranty term

1. Under the terms of this warranty, if failure occurs under normal usage within warranty period, Helior Technology will provide free maintenance based on the proof-documents.

2. If Failure or damage occurs due to incorrect operation, wire connection, or any other mis-opeartions, Helior Technology will provide pay maintenance on charge basis.

More detailed info for family UPS & Inverter, please do not hesitate to inquiry now!



Copyright Notice @ 2008-2022 ECOL Limited and/or its subsidiaries and licensors. All rights reserved.