- Contact Person : Mr. Wen Edwin
- Company Name : Helior Technology Co., Ltd.
- Tel : 86-0755-83979799
- Fax : 86-0755-83978200
- Address : Guangdong,Shenzhen,District Two of Tower B, Tower A, 3/F, Xixiang Haibin Industrial Zone
- Country/Region : China
- Zip : 518102
Related Product Searches:Module design three phase 120kva ups systems (3V3 Vector 15-120KVA),High Quality three phase 120kva ups systems,three phase 120kva ups systems 3V3-VECTOR 15-120KVA
Module design three phase 120kva ups systems (3V3 Vector 15-120KVA)
Outstanding feature
1. High input Power factor for over 0.99
2. Equipped with DSP innovative
3. Add up external battery system
4. Dual communication interface
5. Available for Generator input
6. With specialized monitoring software to monitor or remote control the system
7. Wide input range
8. Cold start
9. High Efficiency
10. Short Circuit protection
11. Support SNMP application (Option)
12. Support AS400 Dry – Contract interface(Option)
Technical Specifications | ||||||
MODEL | VECTOR 15KVAS | |||||
Power(VA/Watt) | 15KVA/12KW | |||||
INPUT | ||||||
Voltage & Voltage Range | 380 VAC, 3 Phase + Neutral | |||||
Voltage Tolerance | 204 – 520 VAC | |||||
BYPASS Voltage Range | 323 - 437 VAC / 380 x (1 ± 15%) VAC | |||||
Power Factor | ≥ 0.99 | |||||
Current THD | <5% | |||||
Frequency & Frequency Range | 40 ~ 70 Hz | |||||
Working with Gen Set | Perfect Voltage and frequency Compatibility | |||||
OUTPUT - INVERTER and BYPASS | ||||||
Power Factor | 0.8 | |||||
Voltage Wave Form | Sinusoidal | |||||
Voltage & Voltage Tolerance | 380 x (1 ± 2%) VAC | |||||
Frequency & Frequency Range | Synchronize with the input AC Power (Line Mode) - when the input frequency of AC Power is out of ± 8%, output frequency is 50 x (1 ± 0.5%)Hz | |||||
Over Load (Mains) | For 110% - 130% load 10 mins. | |||||
For 130% - 150% load transfer to bypass after 1 min | ||||||
For >150% load for 0.5s | ||||||
Short Circuit Protection | Electronic short circuit protection | |||||
BATTERY | ||||||
Type and Placement | Maintenance Free, Dry Type, Internal | |||||
Capacity and Number | 12 V x 40 pcs | |||||
Nominal Battery Voltage | + Battery Group: + 240 VDC; - Battery Group: - 240VDC | |||||
Battery Charging Current | 4.5 Ampere (Constant Current) | |||||
INDICATORS & CONTROL PANEL | ||||||
Type | LCD Panel | |||||
GENERAL | ||||||
Total Efficiency | > 90% | |||||
Noise Level | < 62 dBA | |||||
Electro Magnetic Compatibility | EN 61000-4-2 (ESD), 4-3 (RS), 4-4 (EFT), 4-5 (surge), IEC 62040-2 (EMI) | |||||
Operation Temperature and Humidity | 0 °C ~ 40 °C, maximum 20-90% (Non Condence) | |||||
Storage Temperature | -25 °C ~ +55 °C | |||||
Cooling Type | Forced cooling with variable speed fan according to load % | |||||
Dimensions (mm), W x H x D | 260 x 717 x 570 (Only UPS, Battery not included) | |||||
Weight W/O / W/Battery (kg) | 50 |
Customer Feedback
Our R&D team have tested your UPS, they are satisfied with the performance of the sample. All the test
results are complying with the specification. We are highly appreciated it. --- N. Raja (from Chennai, India)
We are quite impressive with the IGBT function of this UPS. We are now trying to apply this model on our
telecommunication systems. --- Robert Alles (from Munich, Germany)
Order information
Trade term: FOB Shenzhen / Hongkong
Delivery time: 7-21 days after confirmed the order
Packaging Detail:Standard export carton or OEM package
Warranty
1 years since the date of purchase
Warranty term
1. Under the terms of this warranty, if failure occurs under normal usage within warranty period, Helior Technology will provide free maintenance based on the proof-documents.
2. If Failure or damage occurs due to incorrect operation, wire connection, or any other mis-opeartions, Helior Technology will provide pay maintenance on charge basis.
More detailed info for family UPS & Inverter, please do not hesitate to inquiry now!